Can I Add A Vfd After The Disconnect?

I just spent $900 on my RPC unit. I don't think I'm getting rid of it. I also use it to power my 5 HP lathe. It's a 10HP american rotary RPC. VFD's keep leaving me feeling very very frustrated .


That changes things a bit. Since you have a RPC it's safe to assume that your shop is supplied with single phase power. I would use the RPC to power the lathe and other equipment as needed and run another line from the single phase panel to the mill, then run the mill with the VFD.

The reason you are not getting a definitive answer to your original question is that nobody has run a VFD off of a RPC, so no experience with that arrangement. Will it work? Probably, but the RCP outputs a odd wave form so nobody is willing to say 'Yeah, that'll work''. I'm not going to try to give a detailed technical explanation here, but the wave form of single phase is 2 legs 180 degrees, the wave form of 3 phase from the power company is 3 legs that are 120 degrees, but the wave form from a RCP is somewhere in between and is load dependent. So not sure how the VFD will react.

On a 1/2 hp motor, I might be tempted to get a 120V input VFD (240V, 3 phase out), and just plug the mill into the nearest outlet. Here is an example of that type VFD
http://www.automationdirect.com/adc...ts_(115_-z-_230_-z-_460_-z-_575_VAC)/GS2-10P5

Or just run another 240V line from the single phase panel and run the mill with a single phase input VFD.
.
.
 
That changes things a bit. Since you have a RPC it's safe to assume that your shop is supplied with single phase power. I would use the RPC to power the lathe and other equipment as needed and run another line from the single phase panel to the mill, then run the mill with the VFD.

The reason you are not getting a definitive answer to your original question is that nobody has run a VFD off of a RPC, so no experience with that arrangement. Will it work? Probably, but the RCP outputs a odd wave form so nobody is willing to say 'Yeah, that'll work''. I'm not going to try to give a detailed technical explanation here, but the wave form of single phase is 2 legs 180 degrees, the wave form of 3 phase from the power company is 3 legs that are 120 degrees, but the wave form from a RCP is somewhere in between and is load dependent. So not sure how the VFD will react.

On a 1/2 hp motor, I might be tempted to get a 120V input VFD (240V, 3 phase out), and just plug the mill into the nearest outlet. Here is an example of that type VFD
http://www.automationdirect.com/adc...ts_(115_-z-_230_-z-_460_-z-_575_VAC)/GS2-10P5

Or just run another 240V line from the single phase panel and run the mill with a single phase input VFD.
.
.
An RPC (as opposed to a "static comverter") supplies true three-phase, though the voltage of the generated phase may droop a little. However, it is not balanced with respect to the neutral of the single-phase source. I've never used a three-phase VFD but I'm guessing that the full-wave bridge in it would need the three-phase neutral. A three-phase VFD might or might not work if you just hook it up to your RPC. I second Jim's suggestion.
 
I did a recent install that had single phase to an 10Hp RPC and a distribution panel to multiple machines (10+). Some used VFDs at the machine for variable speed and braking requirements. We equipped a plate roller with a Hitachi WJ200 VFD (3 Phase input) running the plate roller 2Hp drive motor, the height motor ran directly off the 3 phase RPC, the electronics required another separate DC supply and used a step down transformer for the 120VAC hour meter. There were no issues or problems. RPCs are used to run CNC machines that use VFDs. Since a VFD rectifies the incoming AC to DC and then the output is regenerated back to 3 phase AC, I am not clear on the issue, but I am only going on posted manufacturer information on the topic. There may be some derating factor of the VFD based on the quality of the 3 phase power and the phasing. Yes, KISS is fine, but with a shop full of machines with different power requirements, you try to do the most logical and practical approach. You also reach limitations of motor sizing when using a single phase input VFD. Contact American Rotary and see if there unit will work with a VFD and if their are any limitations or issues, or what they recommend.

http://www.kayind.com/tech_center/FAQ.htm
Can I operate a motor with a variable speed (variable frequency) drive (VFD)? (off of a RPC)
Absolutely. And don't believe anyone who says otherwise. Just be sure to make it clear that you will be powering a VFD because it may change the size recommendation.

So you need to decide what is the easiest option for you, you could run a separate single phase branch circuit to the mill, or you could use the current RPC 3 phase and power the VFD from that. Many VFD are rated based on single phase input or 3 phase input, so you should use a VFD that is matched to the input power and the mill motor rating. Some of the smaller VFD can be wired for 1 or 3 phase input (see VFD specs). So you would wire the incoming power to the VFD and the output of the VFD directly to the mills 3 phase motor. You could use a power disconnect switch or a plug before the VFD to break the power. You would use the VFD main panel or wire switches and a pot to the input terminals to control the direction and speed. You would probably use a 1HP VFD for the mill.
 
My take on it is......why fire up the RPC just to run a 1/2 HP VFD? Seems like a waste of energy. Do what JimDawson said....plug the VFD into a 120v outlet and simplify your life. Save the RPC for when you need it for the lathe or anything else you get in the future.

Chris
 
There is no need to run the 3 phase convertor. Just buy a suitable VFD that has adequate horsepower and connect it to either 110 V or 220V as specified in the documentation. One thing to keep in mind, your forward/reverse switch on your mill will not work with most VFD's . Just leave it in forward position and use the VFD to start (either FWD or REV) and stop the mill. At least on my setup when I start the VFD first and then try to connect a motor, I get an overload condition on the VFD, probably due to high start-up current of the motor.
 